FS 117 W
2 hour gypsum wall. Max. 24" sch 10 steel pipe, max. 5" EMT or conduit, max. 6" copper pipe. Min. 1-1/4" depth of fill material. Also referred to as FS117W.
|
 |
FS 118 W
2 hour gypsum wall. Max. 24" sch 10 steel pipe, max. 5" EMT or conduit, max. 6" copper pipe. Min. 5/8" depth of fill material. Also referred to as FS118W.
|
 |
FS 119 W
2 hour gypsum wall. Max. 24" sch 10 steel pipe, max. 5" EMT or conduit, max. 6" copper pipe. Max. 1" thick glass fiber insulation. Min. 1-1/4" depth of fill material. Also referred to as FS119W
|
 |
FS 120 W
2 hour gypsum wall. Max. 24" sch 10 steel pipe, max. 5" EMT or conduit, max. 6" copper pipe. Max. 1" thick glass fiber insulation. Min. 5/8" depth of fill material. Also referred to as FS120W.
|
 |
PV 120-08
Max 8 in. steel, max 8 in. cast iron, max 6 in. EMT, max 6 in. copper, max 1/2 in. BX, max 2 in. PVC, max 2 in. CPVC, max 1-3/16 in. Kitex, max 4 in. cable bundle. See chart in system for opening size and annular space. Canadian test pressure differential 2.5 Pa. 2 hour F rating. Also known as PV12008.
|
 |
W-L-1001
12" steel, cast iron, 6" conduit or EMT, 6" copper. Also referred as WL1001.
|
 |
W-L-1003
12" steel, 12",cast iron, 6" conduit, 6" copper, 4" EMT, 28 gauge steel sleeve. Concentric or eccentric installation. Point contact to max 2-3/4" annular. Max opening 15 in. U300,U400, or V400 series walls.1&2 hour F rating. No T rating. Also known as WL1003.
|
 |
W-L-1009
12" steel, 4" EMT, conduit, 2" copper. Also referred as WL1009.
|
 |
W-L-1010
24" steel, 6" copper, 4" EMT, conduit. Also referred as WL1010.
|
 |
W-L-1016
3" steel or EMT: 12" 28 gauge steel sleeve. Also referred as WL1016.
|
 |
W-L-1017
4" steel or aluminum flexible conduit. Also referred as WL1017.
|
 |
W-L-1032
2" aluminum flexible conduit. Also referred as WL1032.
|
 |
W-L-1037
2" steel, EMT or copper. Also referred as WL1037.
|
 |
W-L-1073
4" steel or aluminum flexible conduit: 28 gauge steel sleeve. Also referred as WL1073.
|
 |
W-L-1077
1" flexible metal piping. Also referred as WL1077.
|
 |
W-L-1080
4" steel, EMT, cast iron, conduit, 2" copper. Also referred as WL1080.
|
 |
W-L-1096
1" flexible metal piping. Also referred as WL1096.
|
 |
W-L-1133
6 in. steel, 6 in. cast or ductile iron, 4 in. EMT or steel conduit. Max diam of opening 11-1/2 in. Concentric or eccentric installation. Point contact to max 7/8 in. annular between pipe covering and opening. 12 in. long 2 in. thick fiberglass jacketing required. 1 hour F Rating.Caulk only system. Also known as WL1133.
|
 |
W-L-1137
Max 6 in. No. 11 MSG alumimum pipe with beverage lines of max 12 1/2 PE and max 2 1/2 in. copper bundled within 3/4 in. AB/PVC or max 10 3/8 polyolefin tubes bundles within PVC jacket and 3/4 in. AB/PVC insulation. Up to 45 degree angle. Sleeve required. Max opening 1/2 in. larger than OD of sleeve. See system for annular. 1 hour F. Also known as WL1137.
|
 |
W-L-1146
24" steel, iron, cast iron, 6" conduit, copper tubing, copper pipe, 4" EMT. Also referred as WL1146.
|
 |
W-L-1157
24" schedule 10 steel, iron, 6" copper tubing or copper pipe. Also referred as WL1157.
|
 |
W-L-1166
4" copper tubing or pipe, steel pipe, conduit, iron, EMT. Also referred as WL1166.
|
 |
W-L-1167
12" steel, cast iron, 4" EMT, 4" copper tubing or pipe, 6" conduit. Also referred as WL1167.
|
 |
W-L-1202
24" steel, cast, iron, 6" conduit, 4" EMT, 6" copper. Also referred as WL1202.
|
 |
W-L-1228
Multiple 2" steel conduit, EMT. Also referred as WL1228.
|
 |
W-L-1255
4" EMT multiple, 225 sq. in., 22-1/2" maximum. Also referred as WL1255.
|
 |
W-L-1287
Multiple 3" steel, iron, cast, 2" copper tubing or pipe, 2" flexible metal piping. Also referred as WL1287.
|
 |
W-L-1296
8" steel,8" iron, 8"cast iron, 6" rigid steel conduit, 4" EMT, 4" conduit, 4"copper tubing or pipe. See system for metal gas piping details. U300, U400, V400 series walls. Point contact to max 2 in. annular. Max opening 10-5/8". Concentric or eccentric installation. Optional 28 ga. steel sleeve.1 & 2 hour F rating. See system for T rating. Also known as WL1296.
|
 |
W-L-1299
Multiple max. 3" steel pipes or conduits through max. 182 sq. in. with max. dimension of 14-1/2". Also referred as WL1299.
|
 |
W-L-1310
Max: 4" steel pipe, 4" conduit (EMT), 4" iron pipe, 4" copper pipe, 4"copper tubing. Max diameter of opening 6-1/2". Steel sleeve. One sided application. Shaft wall. 2 hour F rating. Concentric or eccentric installation. Mineral wool required. Also known as WL1310.
|
 |
W-L-1323
Max. 10" steel pipe, cast iron pipe and max. 4" copper pipe or tubing. 3M Fire Barrier Duct Wrap 20A to extend min. 24" from each surface of wall assembly. Also referred as WL1323.
|
 |
W-L-1340
8" steel, 8" iron, 4" EMT, 6" rigid steel conduit, 4" copper pipe or tubing. Max opening 12". Concentric or eccentric installation. Angle of installation up to 45 degrees from perpindicular. Annular point contact to max 3-1/2". 1 & 2 hr. F. Also known as WL1340.
|
 |
W-L-1341
6" steel, 6" iron, 4" EMT, 6" rigid steel conduit, 3" copper pipe or tubing. Diam of opening min 1/2" to max 4" greater than outside diam of penetrant. Penetrant centered. Annular min 1/4" to max 2". 1 & 2 hr F. Also known as WL1341.
|
 |
W-L-1353
2" steel, 2" iron, 2" copper pipe, 2" copper tubing penetrates one side of wall. Penetrant connected to metal tee for closed or vented systems. Point contact to max 1" annular. 1 & 2 Hour F Rating. Also known as WL1353.
|
 |
W-L-1391
Square device:max area 98-1/2 sq. in. w/ max dimension of 12-1/8 in. Round device:max diam of opening 4-1/2 in. One or more penetrants through each device w/ concentric or eccentric installation.Max 3 in. steel,max 3 in. iron,max 3 in. copper tubing,max 3 in. copper pipe,max 3 in. EMT, max 1-4 in. flexible metal piping. Max 6 square devices ganged or 1 round.1 and 2 hour F.Also known as WL1391.
|
 |
W-L-1413
Max 8 in. steel, max 8 in. iron, max 6 in. conduit, max 4 in. EMT, max 6 in. copper tubing, max 6 in. copper pipe. Max diam of opening 10 in. U400 or V400 series gypsum shaft wall assembly. Concentric or eccentric installation. Point contact to max 2 in. annular. 1 and 2 hour F rating. Caulk only system. Also known as WL1413.
|
 |
W-L-1414
Max 3 in. steel,max 3 in. iron,max 3 in. conduit,max 3 in. EMT, max 3 in. copper tubing,max 3 in. copper pipe,max 1 in. flexible metal piping. Max diam of opening 4-1/2 in. U400 or V400 series gypsum shaft wall assembly. Multiple penetrants.Concentric or eccentric installation. Point contact to max 2 in. annular. 1/4 to 1 in. space between penetrants.1 & 2 hour F rating. Also known as WL1414.
|
 |
W-L-1426
U300, U400 or V400 wall. Max 4 in. steel, max 4 in. cast iron, max 4 in. ductile iron. Concentric or eccentric installation. Max diam of opening 5-1/2 in. Compression coupling installed partially in opening with min 1/2 in. protruding. Point contact to max 1/2 in. annular space. Caulk only system. 1 & 2 hour F. Also known as WL1426.
|